What should be paid attention to before the start of the gas pressure regulating box


Release time:

2020-01-03

The box body of the gas pressure regulating box can be made into ordinary type or heat preservation (heating) type according to the temperament. For dry, non-water temperament (such as natural gas, etc.), can choose ordinary type box. For the water content and the temperament (such as artificial gas, liquefied petroleum gas, etc.) that is greatly affected by temperature changes, the heat preservation box must be selected to ensure the normal gas supply of the pressure regulating system.

Before starting the gas pressure regulating tank, confirm that the inlet and outlet valves and bypass valves are closed;
2. Remove the blind plates at both ends of the regulator;
3. Before commissioning, the external pipeline shall be purged, and the ventilation operation can be carried out only after it is confirmed that there is no mixed gas;
4. Slowly open the inlet valve, connect one end of the double-headed cock on the outlet side to the pressure gauge, and connect a hose to the other end to lead out of the box. Turn on the double-headed cock. If you hear the sound of airflow, the device is activated. At this time, the output pressure of the gas pressure regulating tank can be adjusted to the required pressure according to the display of the pressure gauge. If there is no adjustment margin between the output pressure and the required pressure, replace the corresponding pressure regulating spring and readjust the gas pressure regulating box;
5. Slowly close one end of the double-headed cock hose and observe whether the closing pressure displayed by the pressure gauge is normal. After the commissioning is qualified, slowly open the outlet valve of the gas pressure regulating tank to start gas supply; if it is abnormal, please overhaul the gas pressure regulating tank according to the operation instruction, and then supply gas after the overhaul is qualified;
6. In the two-way gas pressure regulating tank, debug the other way from step 2. After the debugging is completed, close the inlet and outlet valves of the road;
7. For the gas pressure regulating tank equipped with overpressure relief valve, adjust the overpressure relief valve after the debugging is normal. Set the bleed pressure as 1.3 times of the output pressure, and open the valves before and after the bleed valve to ensure its normal operation;
8. For gas pressure regulating box equipped with overpressure cut-off valve, the cut-off pressure shall be set at 1.5 times of the output pressure. The box body of the gas pressure regulating box can be made into ordinary type or heat preservation (heating) type according to the temperament. For dry, non-water temperament (such as natural gas, etc.), can choose ordinary type box. For the water content and the temperament (such as artificial gas, liquefied petroleum gas, etc.) that is greatly affected by temperature changes, the heat preservation box must be selected to ensure the normal gas supply of the pressure regulating system.

Key words:


Previous

Next

Previous:

Next:

More Information

Hebei Ouyi Nuo Gas Equipment Co., Ltd. uses industrial X-ray flaw detection device application project notice.

Our unit has verified the environmental impact assessment, implementation of environmental protection measures, environmental management and site of the "Application Project of Industrial X-ray Flaw Detection Device Used by Hebei Ouyi Nuo Gas Equipment Co., Ltd."

15 gas "dry goods" common sense

A room or kitchen equipped with gas equipment and facilities such as gas meters, gas stoves and gas pipes must not be used as a bedroom or lounge, because if the gas meters, gas stoves and gas pipes are damaged and leaked, it is not easy to detect, and it is more likely to cause explosions, fires, etc. Danger.

Hebei Ouyi Nuo Gas Equipment Co., Ltd. Established Hebei Province A- level R & D Center

With the support of relevant departments in Hebei Province, the company adheres to the attitude of striving for excellence in products. The company has put forward a large amount of funds to dissect and develop the gas regulator, improve it again and again, and finally achieve certain results.

OUYINUO

Address:

No. 6 Weiqi Street, Hengshui Innovation Port South District, Zaoqiang County, Hengshui City, Hebei Province

Hotline:

Business License